Functions
6.5 [2.04] Settings > Limits
Operating with the Local User Interface
Operating Manual, 06/2017, A5E31930478-05
109
1. Component > Main menu > "2. Settings" > "04 Limits"
The menu has two navigation lines for setting alarm limits and/or warning limits. Each
limit range has a minimum and maximum limit that can be activated separately:
Structure of the navigation line for each limit
Limit number. Message level
1)
<
>
2)
Minimum
value
3)
<
>
2)
Maximum
value
3)
Unit
Edit
1)
Limit triggers an alarm or warning.
2)
Monitoring indicator: Activation status of the minimum or maximum value or monitoring range
(monitoring inside/outside). Display in measuring mode only!
3)
Display of minimum/maximum value with activation only, otherwise "-"
2. Open selected limit range: Press <ENTER>.
3. Set values:
– Enable/disable values: "Min active" and/or "Max active" parameter fields.
– Authorize access with Standard PIN, if necessary.
– Enter values: "Minimum value" and/or "Maximum value" parameter fields
4. Set the monitoring range: "Limits violated at" parameter field.
Select a range in which there is a limit violation (limit violation caused by measured
values outside or within a band): → Table 6-2 Monitoring options using limits (Page 108).

Table of Contents

Other manuals for Siemens SIPROCESS GA700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROCESS GA700 and is the answer not in the manual?

Siemens SIPROCESS GA700 Specifications

General IconGeneral
BrandSiemens
ModelSIPROCESS GA700
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals