EasyManuals Logo

Siemens SIPROCESS GA700 User Manual

Siemens SIPROCESS GA700
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #176 background imageLoading...
Page #176 background image
Functions
6.9 [2.10] Settings > Correction of cross-interferences
Operating with the Local User Interface
176 Operating Manual, 06/2017, A5E31930478-05
Procedure
Note
Order of the settings
The following applies before you activate correction of cross
-interference in the application
"H
2
in N
2
(Q)" (" application 'furnace gas ', 'converter gas' and ‘wood distillation'"):
•
Make sure that you keep to the order described below.
•
If necessary, check the interference gas assignment in the menu [2.10]: → Setting the
correction of cross-interference (Page 168).
1. Setting the interference gas 1: Component > Main menu > "2. Settings" > "10. Correction
of cross interference" > "3 ..."
– For the "Measured value" parameter, set the value "Gas 1: CO
2
. Correction: 0 to 30%
– Set the measured value source to "Analog input" or "MODBUS TCP"
2. Setting the interference gas 2: Component > Main menu > "2. Settings" > "10. Correction
of cross-interference" > "4 ..."
– For the "Measured value" parameter, set the value "Gas 2: CO. Correction: 0 ... 100%
– Set the measured value source to "Analog input" or "MODBUS TCP"
3. Setting the interference gas 3: Component > Main menu > "2. Settings" > "10. Correction
of cross interference" > "5..."
– For the "Measured value" parameter, set the value "Gas 3: CH
4
. Correction: 0 to 10%
– Set the measured value source to "Analog input" or "MODBUS TCP"
4. Additional settings per interference gas: → Assigning variable correction of cross-
interference (Page 177).
6.9.8.2
Assigning correction of cross-interference with a constant
Procedure with CALOMAT 7
1. Component > Main menu > "2. Settings" > "10. Correction of cross-interference" > "2
Constant"
2. Enable/disable correction of cross-interference: "Correction of cross-interference"
parameter field.
Authorize access with Expert PIN, if necessary.
3. Enter constant already known: "Constant" parameter field. The measured value is
corrected by the amount entered.

Table of Contents

Other manuals for Siemens SIPROCESS GA700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROCESS GA700 and is the answer not in the manual?

Siemens SIPROCESS GA700 Specifications

General IconGeneral
BrandSiemens
ModelSIPROCESS GA700
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals