Appendix
A.5 MODBUS TCP
Operating with the Local User Interface
286 Operating Manual, 06/2017, A5E31930478-05
A status byte is additionally transmitted in synchronism with each measured value. This byte
provides information on the quality of the value in the form of a "Status code". The status
byte has the following structure:
Table A- 8 Coding of status byte/structure
1 0 good
1)
1)
With limit violations within one band
Coding of the status byte for the measured value output
Table A- 9 Measured value status "Good" (MODBUS TCP)
The measured value is valid, but is below an alarm limit.
The measured value is valid, but is above an alarm limit.
1 0 0 0 1 1 1 1 143 0x8f The measured value is valid, but is within an invalid alarm
-
The measured value is valid, but is below a warning limit.
The measured value is valid, but is above a warning limit.
1 0 0 0 1 0 1 1 139 0x8b The measured value is valid, but is within a warning limit
-
1 0 1 1 1 1 0 0 188 0xbc The measured value is valid, but the function check is ac-
tive.
For example, measuring mode is active and a user is logged
on.
-
1 0 1 0 1 0 0 0 168 0xa8 The measured value is valid, but a maintenance demanded
-
1 0 1 0 0 1 0 0 164 0xa4 The measured value is valid, but a maintenance demanded
-
The measurement is valid (normal measuring mode).