EasyManua.ls Logo

Siemens SIPROTEC 4 7VE61 - Page 281

Siemens SIPROTEC 4 7VE61
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addr. Parameter Function Setting Options Default Setting Comments
7311 ANALOGOUTPUT B1 AnalogOutputs U1 [%]
f1 [%]
U2 [%]
f2 [%]
ΔU [%]
Δf [%]
Δα [%]
|ΔU| [%]
|Δf| [%]
|Δα| [%]
ΔU [%] Analog Output B1 (Port B)
7312 MIN. VALUE(B1) AnalogOutputs -200.00 .. 100.00 % -50.00 % Minimum Percentage
Output Value (B1)
7313 MIN. OUTPUT(B1) AnalogOutputs 0 .. 10 mA 4 mA Minimum Current Output
Value (B1)
7314 MAX. VALUE(B1) AnalogOutputs 10.00 .. 200.00 % 50.00 % Maximum Percentage
Output Value (B1)
7315 MAX. OUTPUT(B1) AnalogOutputs 10 .. 22 mA 20 mA Maximum Current Output
Value (B1)
7321 ANALOGOUTPUT B2 AnalogOutputs U1 [%]
f1 [%]
U2 [%]
f2 [%]
ΔU [%]
Δf [%]
Δα [%]
|ΔU| [%]
|Δf| [%]
|Δα| [%]
ΔU [%] Analog Output B2 (Port B)
7322 MIN. VALUE(B2) AnalogOutputs -200.00 .. 100.00 % 0.00 % Minimum Percentage
Output Value (B2)
7323 MIN. OUTPUT(B2) AnalogOutputs 0 .. 10 mA 4 mA Minimum Current Output
Value (B2)
7324 MAX. VALUE(B2) AnalogOutputs 10.00 .. 200.00 % 100.00 % Maximum Percentage
Output Value (B2)
7325 MAX. OUTPUT(B2) AnalogOutputs 10 .. 22 mA 20 mA Maximum Current Output
Value (B2)
7331 ANALOGOUTPUT D1 AnalogOutputs U1 [%]
f1 [%]
U2 [%]
f2 [%]
ΔU [%]
Δf [%]
Δα [%]
|ΔU| [%]
|Δf| [%]
|Δα| [%]
ΔU [%] Analog Output D1 (Port D)
7332 MIN. VALUE(D1) AnalogOutputs -200.00 .. 100.00 % 0.00 % Minimum Percentage
Output Value (D1)
7333 MIN. OUTPUT(D1) AnalogOutputs 0 .. 10 mA 4 mA Minimum Current Output
Value (D1)
Functions, Settings, Information
E.2 Settings
SIPROTEC 4, 7VE61 and 7VE63, Manual 281
C53000-G1176-C163-3, Edition 10.2017

Table of Contents