Addr. Parameter Function Setting Options Default Setting Comments
7334 MAX. VALUE(D1) AnalogOutputs 10.00 .. 200.00 % 100.00 % Maximum Percentage
Output Value (D1)
7335 MAX. OUTPUT(D1) AnalogOutputs 10 .. 22 mA 20 mA Maximum Current Output
Value (D1)
7341 ANALOGOUTPUT D2 AnalogOutputs U1 [%]
f1 [%]
U2 [%]
f2 [%]
ΔU [%]
Δf [%]
Δα [%]
|ΔU| [%]
|Δf| [%]
|Δα| [%]
ΔU [%] Analog Output D2 (Port D)
7342 MIN. VALUE(D2) AnalogOutputs -200.00 .. 100.00 % 0.00 % Minimum Percentage
Output Value (D2)
7343 MIN. OUTPUT(D2) AnalogOutputs 0 .. 10 mA 4 mA Minimum Current Output
Value (D2)
7344 MAX. VALUE(D2) AnalogOutputs 10.00 .. 200.00 % 100.00 % Maximum Percentage
Output Value (D2)
7345 MAX. OUTPUT(D2) AnalogOutputs 10 .. 22 mA 20 mA Maximum Current Output
Value (D2)
8501 MEAS. VALUE 1> Threshold Disabled
Ua
Ub
Uc
Ud
Ue
Uf
Disabled Measured Value for
Threshold MV1>
8502 THRESHOLD MV1> Threshold 2 .. 200 % 100 % Pickup Value of Measured
Value MV1>
8503 MEAS. VALUE 2< Threshold Disabled
Ua
Ub
Uc
Ud
Ue
Uf
Disabled Measured Value for
Threshold MV2<
8504 THRESHOLD MV2< Threshold 2 .. 200 % 100 % Pickup Value of Measured
Value MV2<
8505 MEAS. VALUE 3> Threshold Disabled
Ua
Ub
Uc
Ud
Ue
Uf
Disabled Measured Value for
Threshold MV3>
8506 THRESHOLD MV3> Threshold 2 .. 200 % 100 % Pickup Value of Measured
Value MV3>