Addr. Parameter Function Setting Options Default Setting Comments
8507 MEAS. VALUE 4< Threshold Disabled
Ua
Ub
Uc
Ud
Ue
Uf
Disabled Measured Value for
Threshold MV4<
8508 THRESHOLD MV4< Threshold 2 .. 200 % 100 % Pickup Value of Measured
Value MV4<
8509 MEAS. VALUE 5> Threshold Disabled
Ua
Ub
Uc
Ud
Ue
Uf
Disabled Measured Value for
Threshold MV5>
8510 THRESHOLD MV5> Threshold 2 .. 200 % 100 % Pickup Value of Measured
Value MV5>
8511 MEAS. VALUE 6< Threshold Disabled
Ua
Ub
Uc
Ud
Ue
Uf
Disabled Measured Value for
Threshold MV6<
8512 THRESHOLD MV6< Threshold 2 .. 200 % 100 % Pickup Value of Measured
Value MV6<
8601 EXTERN TRIP 1 External Trips OFF
ON
Block relay
OFF External Trip Function 1
8602 T DELAY External Trips 0.00 .. 60.00 sec 1.00 sec Ext. Trip 1 Time Delay
8701 EXTERN TRIP 2 External Trips OFF
ON
Block relay
OFF External Trip Function 2
8702 T DELAY External Trips 0.00 .. 60.00 sec 1.00 sec Ext. Trip 2 Time Delay
8801 EXTERN TRIP 3 External Trips OFF
ON
Block relay
OFF External Trip Function 3
8802 T DELAY External Trips 0.00 .. 60.00 sec 1.00 sec Ext. Trip 3 Time Delay
8901 EXTERN TRIP 4 External Trips OFF
ON
Block relay
OFF External Trip Function 4
8902 T DELAY External Trips 0.00 .. 60.00 sec 1.00 sec Ext. Trip 4 Time Delay
Functions, Settings, Information
E.2 Settings
SIPROTEC 4, 7VE61 and 7VE63, Manual 283
C53000-G1176-C163-3, Edition 10.2017