EasyManuals Logo

Siemens SIPROTEC 4 7VE61 User Manual

Siemens SIPROTEC 4 7VE61
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
Selection of the synchronizer (measuring quantities connection, interconnection with the circuit breaker
and selection of the synchronizing functional groups)
Start of synchronizing
The synchronism can be started in different ways. An overview can be seen in Figure 2-17.
[sync-startlogik-220403-kn, 1, en_GB]
Figure 2-17
Start logic (illustration for one channel)
The start input
>Sync Start
is to be used with parallel connection. Here a short pulse is sufficient (>100
ms). The information is recorded in the flip-flop and the rest logic is released. Simultaneously, the monitoring
time is started. If this elapses without previous closing, the function is terminated. If a running synchroniza-
tion should be interrupted, the stop input
>Sync Stop
has to be pressed. The stop input is dominant to the
start input. Alternatively synchronization can also be interrupted using the blocking input
>BLOCK Sy1
. The
corresponding indiciation
Sy1 BLOCK
is produced.
The logic described in the individual sections is processed in each procedure separately. The logic shown in
Figure 2-18 uses in time supervision (below right), the same operating mode is monitored - both procedures
must have detected “synchronous switching” or “asynchronous switching” - (upper left) and in the event of
positive conditions both closure commands are issued.
Using the parameter 6001 COM. TESTSYNC. or the binary input
>COM Test sync.
a synchronization test
can be carried out. This synchronization test is started as a normal synchronization. However, the indications
Sync CloseRel 1
and
Sync CloseRel 2
are suppressed, do not press the CLOSE relay BO1 and BO2 and
instead, the indiciations
Test CloseRel 1
and
Test CloseRel 2
are displayed, so long as the
synchronism is successfully established.
Functions
2.2 Paralleling Functions
SIPROTEC 4, 7VE61 and 7VE63, Manual 53
C53000-G1176-C163-3, Edition 10.2017

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 4 7VE61 and is the answer not in the manual?

Siemens SIPROTEC 4 7VE61 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 4 7VE61
CategoryPower distribution unit
LanguageEnglish

Related product manuals