Configuration
4.22 Data points
TIM 1531 IRC
120 Operating Instructions, 02/2018, C79000-G8976-C468-02
Requirements and restrictions
You will find the requirements for the configuration of the preprocessing options and
restrictions in the section relating to the particular function.
Note
Restrictions due to configured triggers
The analog value preprocessing options "Error suppression time", "Limit value calculation"
and "smoothing" are not performed if no threshold value trigger is configured for the rel
evant
data point.. In these cases, the read process value of the data point is entered in the image
memory and transferred transparently before the preprocessing cycle of the threshold value
calculation (500
ms) elapses.