5.7 Master copies
TIM 1531 IRC
222 Operating Instructions, 02/2018, C79000-G8976-C468-02
Parameter:
NewData
Explanation:
For the declaration, data type, range of values, default and function, refer to
the section
Reoccurring parameters (Page 144).
Whenever the block has received new data and has output it to the outputs
"ReturnedSetpoint" or "LocalOperation", the "NewData" output is set to TRUE
for one OB1 cycle.
Parameter:
SendSoftSetpoint
Declaration:
IN_OUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Address
range:
Bit memory
M 0.0 ... M n.7
Data bit
DBm.DBX 0.0 ... n.7
This is an in/out parameter (declaration IN_OUT). It is difficult to specify local
bit memory with this parameter type and this should not be used.
Explanation:
Trigger input for resending the last software setpoint.
For further details, refer to the "SetpointInput" parameter.
If you do not require the parameter, simply leave it open.
5.7.1.22
Setpoint typical Set01W_R
Function
Receive 1 setpoint in the station as a 16 bit value or enter locally and return the local
setpoint to the master station
Parameter
Parameter:
PartnerNo
PartnerObjectNo
Enabled
ImageMemory
Conditional
Unconditional
TimeStamp
For a description, see section Reoccurring parameters (Page 144).