Configuration 
  4.23 Messages 
TIM 1531 IRC 
Operating Instructions, 02/2018, C79000-G8976-C468-02 
127 
 
Partner stations 
Enabling the partner for the ST7 data point 
Enable all partners to which a telecontrol connection was configured and with which the 
selected data point will exchange data. To do this select the relevant " 
" check box. 
You can configure or change the partners in the overview table or in the "Partner stations" 
tab of the module. The data will be adopted at the other point. 
 
Messages 
Configuring e-mails 
If important events occur, the TIM can send e-mails to a communications partner. 
You configure the e-mail in STEP 7 in the editor for the data point and message 
configuration. You can find this using the project tree: 
Project > Directory of the relevant TIM 
For the view in STEP 7, refer to the section Data point configuration (Page 104). 
Requirements and necessary information 
Remember the following requirements in the configuration for the transfer of messages: 
●  Enabling telecontrol communication ("Communication types") parameter group 
●  SMS: Configuration of the SMSC in the "SMSC" parameter group 
●  E-mails: Configuration of the "E-mail configuration" parameter group 
To do this, you require the following information: 
–  Access data of the SMTP server: Address, port number, user name, password 
–  TIM's own e-mail address 
–  Email address of the recipient 
Here you configure the recipient, the subject and the text of the message. 
In the "Trigger" parameter group you configure triggering for sending the message and other 
parameters. 
● 
E-mail trigger / SMS trigger
 
Specifies the event for which the sending of the message is triggered. 
–  Use PLC tag 
For the trigger signal to send the message, the edge change (0 → 1) of the trigger bit 
"PLC tag for trigger" is evaluated that is set by the user program. When necessary, a