Configuration
4.12 Partner stations
TIM 1531 IRC
80 Operating Instructions, 02/2018, C79000-G8976-C468-02
Releasing access to the Web server
To be able to connect to the Web server of the TIM, access to the Web server must be
enabled for every Ethernet interface, see also section Web server access (Page 72). As
default access is disabled.
"Web server" parameter group
General
●
Enable Web server on this module
Enables data processing in the Web server of the TIM and allows access to this data.
●
Allow access only using HTTPS
Allows access to the Web server only with the secure protocol HTTPS.
●
Enables automatic updating of the displayed values.
If the option is disabled, only the values at the time of connecting to the Web server are
displayed.
●
Select the interval at which you require an update of the displayed values.
Default setting: 30. Permitted range: 5...999
Overview of the interfaces
Here you can see the releasing access to the Web server via the Ethernet interfaces of the
TIM.
You can activate access to the Web server of the TIM via HTTP/HTTPS for each individual
Ethernet interface.
The settings for activation in the parameter groups "Web server access" and "Web server"
are adopted reciprocally in the other parameter group.
The parameter group is only visible when the option "Import" is activated under "Basic
settings" > Configuration (Page 58).
Importing the configuration data from STEP 7 V5
Follow the steps below to import the configuration data from STEP 7 V5
1. In your STEP 7 Professional project, select the TIM into which you want to import the
SDBs from the STEP 7 V5 project.
2. Select the "Partner stations" parameter group.