Configuration
4.9 Ethernet interface
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
71
4.9.2.2
TCP connection monitoring
Ethernet interface > Advanced options > TCP connection monitoring
TCP connection monitoring time
Function: If there is no data traffic within the TCP connection monitoring time, the TIM
sends a keepalive to the communications partner.
Default setting: 10 s. Permitted range: 1...65535 s
TCP keepalive monitoring time
After sending a keepalive, the TIM expects a reply from the communications partner
within the keepalive monitoring time. If the TIM does not receive a reply within the
configured time, it terminates the connection.
Default setting: 1 s. Permitted range: 1...65535 s
4.9.2.3
Transmission settings
Transmission settings
Send conditional spontaneous frames as blocks
Indicates the form of transfer of data frames with the transmission mode "Conditional
spontaneous".
Option enabled
Several data items are collected and sent only when a frame is filled to the maximum.
Option disabled
The data is transmitted spontaneously as a single frame.
The transmission mode "Conditional spontaneous" is set differently for the TD7 versions:
TD7onTIM
In the "Trigger" tab of the data point (data point editor)
TD7onCPU
Via the "Unconditional" parameter of the data point typicals (TD7 blocks)
Max. allowed disruption time
Tolerance time (s) for a detected connection disruption.
If there is still a disruption on the connection when the set time has elapsed, the
disruption is signaled to all accessible connection partners of the disrupted station.
Default setting: 0. Permitted range: 0...255. If you enter 0 (zero), the function is disabled.