5.7 Master copies
TIM 1531 IRC
218 Operating Instructions, 02/2018, C79000-G8976-C468-02
5.7.1.21
Setpoint typical Set01W_S
Function
Send 1 setpoint as a 16 bit value and receive local setpoint from partner
The 1-out-of-n check is performed by FC Safe.
Note
FC Safe required
With Set01W_S, data can only be transferred when the block FC Safe is linked in the end of
the cyclic program, see section
FC Safe (Page 214).
Parameter
Parameter:
PartnerNo
PartnerObjectNo
Enabled
For a description, see section Reoccurring parameters (Page 144).
Parameter:
EnterInput
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Address
range:
Input
I 0.0 ... I n.7
Memory bit
M 0.0 ... M n.7
L 0.0 ... L n.7
Data bit
DBm.DBX 0.0 ... n.7
Explanation:
Enter input for hardware setpoint
The adoption of a setpoint at the "SetpointInput" can be triggered by a signal
edge change.
A signal change at "EnterInput" is only taken into account when "Contin
u-
ousEnterFunct" = FALSE.
If this condition is fulfilled, an edge change 0 1
causes the setpoint entered in "SetpointInput" to be adopted and transferred.
This also applies when the newly entered setpoint is identical to the last se
t-
point transferred.
This method of setpoint adoption is suitable for input vis hardware, for exa
m-
ple via a console or control panel.
It can also be used for entering setpoints at an operator panel (OP). In this the
adoption must be triggered by a function key on the OP.
If you do not require the parameter, simply leave it open.