5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
219
Parameter:
ContinuousEnterFunct
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
TRUE
Explanation:
Apply setpoint continuously for software setpoint
With this parameter, you specify whether the setpoint at "SetpointInput"
should be continuously r
ead in and checked for changes. Changes are
checked by comparison with the last setpoint that was transferred.
This method of setpoint adoption is suitable for input via suitable software. It
can, however, also be used for entering setpoints at an operator
panel (OP) if
the OP does not have a separate function key that can be used to trigger the
input.
If you do not require the parameter, simply leave it open.
Parameter:
SetpointInput
Declaration:
INPUT
Data type:
WORD
Range of
values:
See address ran
ge.
Default:
0 (W#16#0)
Address
range:
Input words
IW0 ... IWn
PIW0 ... PIWn
Memory words
MW0 ... MWn
LW0 ... LWn
Data words
DBm.DBW0 ... n