Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
176 Operating Instructions, 02/2018, C79000-G8976-C468-02
Counted value typicals Cnt01D_S / Cnt04D_S
Function
● Cnt01D_S: Send 1 counted value (32 bits).
● Cnt04D_S: Send 4 counted values (32 bits).
Note that the parameter "DifferenceValue" for forming the difference value can only be
activated at the same time for all four counted values.
For a description, see section Reoccurring parameters (Page 144).
Restore collective command
The restore collective command as a central system memory bit belongs to
the organizational SINAUT system commands.
Set the parameter to TRUE if the counted value transfer is to be triggered by a
re
store collective command.
When the destination subscriber no. (PartnerNo) = 0 (transfer to all), the
restore collective command is taken into account.
When the restore collective command is detected, the currently
accumulated counted value is transferred regardless of other triggers for
transfer. The restore bit is inverted in this counted value.
If in the typical an explicit destination subscriber no. (PartnerNo > 0) is
configured, the restore collective command is evaluated in the
corresponding subscriber object in the central administration.
You can use the parameters "GeneralTriggerCommand" and "TriggerInput" at
the same time. In this case the transfer is triggered both by an edge change
0 → 1 at "TriggerInput" and when a restore collective command is received.