Block library TeleControl ST7 
  5.7 Master copies 
TIM 1531 IRC 
Operating Instructions, 02/2018, C79000-G8976-C468-02 
167 
 
Fault suppression time in seconds.
 
Transmission of an analog value located in the overshoot or undershoot range 
(7FFF
H
 or 8000
H
) is suppressed for the time period specified here. The value 
H
 or 8000
H
 is only sent after this time has elapsed, if it is still pending. If 
the value returns to below 7FFF
H
 or above 8000
H
 again before this time 
elapses, it is immediately sent again as normal. The suppression time is star
t-
ed again for the full duration the next time 7FFF
H
 or 8000
H
 is acquired. 
This is typically used for temporary suppression of current values that may 
occur when powerful pumps
 and motors are started. The analog input may 
exceed the maximum range several times under some circumstances. Su
p-
pression prevents these values from being signaled as faults in the control 
center system.
 
The suppression is adjusted to analog values that a
re acquired by the S7 ana-
log input modules as raw values. These modules return the specified values 
for the overflow or underflow range for all input ranges (also for life
-zero in-
puts). With provided ready values, fault suppression is only possible if thes
e 
also adopt the values 7FFF
H
 or 8000
H
 when there is overshoot or undershoot. 
If this is not the case, the parameter does not need to have a value entered.
 
The parameter can also be used in combination with the mean value calcul
a-
tion for temporary suppress
ion of the values 7FFF
H
 or 8000
H
 (see parameter 
 
If no parameter is specified, the default of 0 seconds applies. An acquired 
value of 7FFF
H
 or 8000
H
 is then sent immediately when it is first detected or, 
with mean value calculation, as
 an invalid mean value for the current mean 
value calculation period. 
 
Analog value typical Ana04W_R 
Function 
Receive 4 analog values as 16-bit values 
 
 
 
 
For a description, see section Reoccurring parameters (Page 144).