Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
170 Operating Instructions, 02/2018, C79000-G8976-C468-02
Range of
values:
0 ... 2147483647
•
As 32 bit binary number
2#0 ... 2#11111111_11111111_11111111_11111111
•
As 32 bit hexadecimal number
DW#16#0 ... DW#16#FFFF_FFFF
Default:
0 (2#0)
Explanation:
Inversion mask
The inversion of input signals can, for example, be useful when using a mi
x-
ture of sensors operating on the open and closed circuit principle.
•
For every input to be inverted enter a 1 at the relevant position in the bit
pattern.
•
For the other inputs enter a 0.
For the assignment of the 32 inputs from "InputByte_1" to "InputByte_4" to the
32 bits of the inversion mask, see the following table.
InputByte_1
InputByte_2
InputByte_3
InputByte_4
Bit
.
7
.
6
.
5
.
4
.
3
.
2
.
1
.
0
.
7
.
6
.
5
.
4
.
3
.
2
.
1
.
0
.
7
.
6
.
5
.
4
.
3
.
2
.
1
.
0
.
7
.
6
.
5
.
4
.
3
.
2
.
1
.
0
2#
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
DW#1
6#
_ _ _ _ _ _ _ _
5.7.1.9
Binary value typical Bin04B_R
Function
Receive 4 bytes of binary information
Parameter
Parameter:
PartnerNo
PartnerObjectNo
Enabled
For a description, see section Reoccurring parameters (Page 144).
Parameter:
OutputByte_1 … _4
Declaration:
OUTPUT
Data type:
BYTE
Range of
values:
See address range.
Default:
0 (B#16#0)