Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
223
Release of the local setpoint input of the data area specified by "LocalSe
t-
A setpoint sent by the partner (master station) is not accepted by the object as
long as "Local" = TRUE.
The current status of the "Local" input is transmitted to the partner together
with a copy of the setpoint which is currently being output at "SetpointOutput"
(setpoint mirror
ing).
When there is a switchover from "Local" = 0 to 1, the last values output at
the "SetpointOutput" output are retained until a new setpoint is entered via
the local input area "LocalSetpointInput".
When there is a switch back from "Local" = 1 to 0, the last value output at
the "SetpointOutput" output is retained until the block receives a new
setpoint from the partner.
Read the note on the "ContinuousEnterFunct" parameter.