Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
156 Operating Instructions, 02/2018, C79000-G8976-C468-02
Parameter
Parameter:
PartnerNo
PartnerObjectNo
Enabled
ImageMemory
Conditional
Unconditional
TimeStamp
For a description, see section Reoccurring parameters (Page 144).
Parameter:
ThresholdIntegration
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Explanation:
Threshold processing according to the integration principle
With this parameter, you can specify whether the integration principle is used
in threshold value processing.
With the default FALSE the threshold value is calculated without integration. In
this case, you can expect less data traffic on the telecontrol line and locally
between CPU and TIM.
Parameter:
ZeroLimitation
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE
/ FALSE
Default:
TRUE
Explanation:
Zero limitation
If this parameter is activated negative values are be suppressed and replaced
with the value 0.
Parameter:
TriggerInput
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Address
range:
Input
I 0.0 ... I n.7
Memory bit
M 0.0 ... M n.7
L 0.0 ... L n.7
Data bit
DBm.DBX 0.0 ... n.7