Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
174 Operating Instructions, 02/2018, C79000-G8976-C468-02
Parameter
Parameter:
PartnerNo
PartnerObjectNo
For a description, see section Reoccurring parameters (Page 144).
Parameter:
Enabled
For the declaration, data type, range of values, default and function, refer to
the section Reoccurring parameters (Page 144).
Typical
-
specific r
e-
sponse:
Enable block processing
If processing is disabled the FB only checks to see if t
he disabled status has
been canceled. Any commands that are still received are not output. The FB
cannot communicate at the organizational level in this status because
Cmd01B_R cannot send or receive Org. frames.
If the "Enabled" input should be made opera
ble by a switch, this local disable
means received commands are no longer output. Since the block is, however,
not capable of sending Org. frames, it cannot report this local block back to
the partner itself. This must be done with another typical, e.g. Bin04B_S.
Parameter:
MultipleOutput
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Explanation:
Simultaneous output of multiple commands permitted
With this parameter, you can specify whether or not several (consecu
tively
received) commands can be output simultaneously; in other words, you spec
i-
fy how the block reacts when a new command is received and the pr
eviously
received command still needs to be output.
Requirement: The command output time has not yet elapsed a
nd the user
program has not yet reset this command.
•
FALSE
Multiple output is not permitted. The newly received command overwrites
the output byte. Any command still pending is therefore reset to 0 unless
the new command is identical to the old one.
•
TRUE
Multiple output is permitted. A newly received command is written to the
current output byte. The command output time is restarted and applies to
all pending commands.
Parameter:
CommandOutputTime
Declaration:
INPUT