EasyManuals Logo

Siemens TIM 1531 IRC User Manual

Siemens TIM 1531 IRC
338 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #192 background imageLoading...
Page #192 background image
Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
192 Operating Instructions, 02/2018, C79000-G8976-C468-02
Range of
values:
See address range
Default:
P#P 0.0 VOID 0
(null pointer)
Address
range:
P#DBxx.DBX yy.0 DWORD zz
•
xx: Data block number 1...32767
•
yy: Byte number
•
zz: Number of double words 1...256 starting at byte number yy
Example:
P#DB20.DBX 100.0 DWORD 200
Remember the periods and spaces when entering the pointer!
Note that the default value (null pointer) is not permitted. A pointer with a real
address must be specified.
Explanation:
Data input area
The ANY pointer addresses the data area in which the data to be acquired is
located. This data area must be within a data block and its length can vary
between 1 and 256 data double words. For information on the possible double
word formats, refer to the section "Function" above.
If the parameter assignment is incorrect (null pointer, length > 256, data area
not a DB), an error message is entered in the diagnostics buffer (event ID
B114, [Info2/3] = 11).
The CPU does not change to STOP. The block is then
no longer processed, however, until the error has been corrected.
Data consistency;
If a data segment to be transferred consists of a maximum of 48 bytes, data
consistency during the transfer is assured.
Parameter:
SendAllBusy
Declaration:
INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Explanation:
Block being processed with "SendAll" = TRUE
This output indicates that the block is currently transferring the data specified
by "Da
taInput". The procedure is activated either by a remote single or gen-
eral request or by a local internal or external trigger.
If "SendAll" is set to TRUE, the transfer of all data is triggered either by inte
r-
nal change control (SendOnChange = TRUE) or by the external "TriggerInput"
(edge change 0
→ 1).
The edge change 0
→ 1 has no effect whatsoever with an external "TriggerIn-
put" as long as "SendAllBusy" indicates TRUE. The edge change 0
→ 1 of
"TriggerInput" only takes effect when "SendAllBusy" = FALSE.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens TIM 1531 IRC and is the answer not in the manual?

Siemens TIM 1531 IRC Specifications

General IconGeneral
BrandSiemens
ModelTIM 1531 IRC
CategoryController
LanguageEnglish

Related product manuals