Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
216 Operating Instructions, 02/2018, C79000-G8976-C468-02
Name:
MaxInputTime
Declaration:
INPUT
Data type:
INT
Range of va
l-
ues:
•
0
Value for unrequired parameter
•
1 ... 32000
Range of values for monitoring time
Explanation:
Monitoring time in ms for commands and setpoints that are input via har
d-
ware.
A monitoring time of at least 30 s is recommended.
If you do not require the parameter, specify 0 (zero).
Name:
ResetError
Declaration:
INPUT
Data type:
BOOL
Range of va
l-
ues:
Input
I 0.0 ... I n.7
Memory bit
M 0.0 ... M n.7
L 0.0 ... L n.7
Data bit
DBm.DBX 0.0 ... n.7
Explanation:
Input for resetting the output GlobalCmdOutputError.
If you do not require the parameter, specify a memory or data bit that always
has signal 0.
Name:
InputOK
Declaration:
OUTPUT
Data type:
BOOL
Range of va
l-
ues:
Output
Q 0.0 ... Q n.7
Memory bit
M 0.0 ... M n.7
L 0.0 ... L n.7
Data bit
DBm.DBX 0.0 ... n.7
Explanation:
Display of the enabling of hardware commands and setpoints
Has a 1 signal as soon as the current entry was enabled, i.e. when the har
d-
war
e command or setpoint was entered correctly.
The display bit goes off when the entry is reset, in other words when the
command key is released or the setpoint entry key "EnterInput" input is r
e-
leased.
If you do not require the parameter, specify a memory o
r data bit in the
memory area of the local data.