Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
235
One bit per subscriber is reserved in the "PartnerStatus" output byte to indicate the status of
the respective subscriber:
FALSE (0):
Subscriber disrupted
Corresponding input parameter not used (= 0)
Subscriber unknown
TRUE (1): Subscriber OK
Parameter
Name:
Partner1 ... Partner8
Declaration:
INPUT
Data type:
INT
Range of
values:
0
Value for unrequired parameter
1 ... 32000
Number of the subscriber to be monitored
Explanation
SINAUT su
bscriber number of the subscriber to be monitored
If a set subscriber number is not found in the administration (DB BasicData),
then (only during startup) an entry is written to the diagnostics buffer (event ID
B101). The CPU does not change to STOP.
The s
tatus of a subscriber with a correct parameter assignment is indicated in
the "PartnerStatus" output byte.
An unknown subscriber is not processed until the error is eliminated. Their
status bits are set to 0.
Name:
PartnerStatus
Declaration:
OUTPUT
Data type:
BYTE
Range of va
l-
ues:
Output bytes
QB0 ... QBn
PQB0 ... PQBn
Memory bytes
MB0 ... MBn
LB0 ... LBn
Data bytes
DBm.DBB0 ... n
Explanation:
Indication of the status of the subscriber to be monitored.
Assignment of the status bits in the "Par
tnerStatus" output byte depending
the parameters Partner1 ... "Partner8":
Bit
.7
.6
.5
.4
.3
.2
.1
.0
Partner
8
7
6
5
4
3
2
1
Value:
0 = partner disrupted, not set in the parameters or unknown
1 = partner OK