Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
254 Operating Instructions, 02/2018, C79000-G8976-C468-02
The following time intervals are permitted:
● Hours: 01, 02, 03, 04, 06, 08, 12, 24
● Minutes: 01, 02, 03, 04, 05, 06, 10, 12, 15, 20, 30, 60
● Seconds: 10, 12, 15, 20, 30, 60
Examples:
● IntervalMode : TRUE
The output "TriggerOutput" is set as follows:
– Hour_Minute : W#16#06FF (every 6 hours)
– Second_Day : W#16#FFFF (at 00:00:00, 06:00:00, 12:00:00 o'clock and ...)
– Month_Year : W#16#FFFF (... at 18:00:00 o'clock)
● IntervalMode : TRUE
The output "TriggerOutput" is set as follows:
– Hour_Minute : W#16#FF30
– Second_Day : W#16#FFFF (at 00:00:00, 00:30:00, 01:00:00 o'clock and ...)
– Month_Year : W#16#FFFF (... at 01:30:00, 02:00:00, 02:30:00 o'clock etc.)
Error message during startup
The FC checks the parameters Hour_Minute, Second_Day und Month_Year in every cycle to
ensure that they keep to the permitted range of values. What is permitted is also dependent
on the "IntervalMode" parameter.
If the parameter assignment is incorrect, an error message is entered in the diagnostics
buffer (event ID B113) only during startup. The CPU does not change to STOP. Afterwards,
the FC checks the parameters without outputting error messages until the error has been
eliminated.
The diagnostics message provides a precise identification of the incorrect parameter
(continuous number of the parameter, i.e. 2, 3 or 4). The causes of the diagnostics message
can be depend on the parameter "IntervalMode".
IntervalMode = FALSE (or 0)
The permitted ranges of values for the parameters Hours, Minutes, Seconds, Day, Month
and Year were not kept to. Apart from FF, the following can be configured:
-59
-12