The Web server (WBM)
6.7 Diagnostics
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
271
Date
Date of the diagnostics event
Event type
The diagnostics messages are classified as follows:
INFO
Information about a special event
WARNING
Warning of a possibly unwanted event
ERROR
Internal error. The TIM starts up.
FATAL
Serious error that impairs or interrupts the operation of the TIM.
Event
Plain text of the diagnostics event
Copy of the diagnostics buffer
Using the button, you save the content of the diagnostics buffer on the PC.
The diagnostics buffer
The diagnostics buffer receives diagnostics messages for internal events and errors. It can
hold a maximum of 200 entries. When the maximum number is exceeded, the oldest entries
are overwritten.
The entries in the diagnostics buffer contain a consecutive number, a classification, a time
stamp and the message text.
Below you will find several examples of events that are entered in the diagnostics buffer:
TIM startup
Change to the configuration
Establishment/abort of the communications connection
Time-of-day synchronization
Power failure