Configuration
4.10 Serial interface > Advanced options
TIM 1531 IRC
76 Operating Instructions, 02/2018, C79000-G8976-C468-02
Connection establishment
Extra transmission time
Time offset (s) with slow networks to prevent premature stopping of connection
establishment.
Default setting: 10. Permitted range: 0...65535. If you enter 0 (zero), the function is
disabled.
The following values are usual:
Mobile wireless networks: 10
Wireless or satellite transmission: 0 .. 1
Call parameters
Dialing command
Dialing command for the local modem
Possible values:
D (AT command)
DP (AT command, pulse dialing)
DT (AT command, tone dialing)
When possible use the dialing command "D".
Dialing prefix
Access number (outside line) for a private branch exchange (typical entry 0 or 9) or for an
alternative telephone provider.
Permitted range: Max. 12 digits
With direct connection to the dial-up network and without an alternative telephone
provider, this parameter can remain empty.
Own phone number
Entry of your own telephone number for the network node including the area code.
Permitted values:
Digits 0 ... 9
Plus character (+) as placeholder for the trunk prefix (usually 00 or 09) before the
international area code
Example: +1230123456789