EasyManuals Logo

Siemens TIM 1531 IRC User Manual

Siemens TIM 1531 IRC
338 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
Configuration
4.10 Serial interface > Advanced options
TIM 1531 IRC
76 Operating Instructions, 02/2018, C79000-G8976-C468-02
Connection establishment
Extra transmission time
Time offset (s) with slow networks to prevent premature stopping of connection
establishment.
Default setting: 10. Permitted range: 0...65535. If you enter 0 (zero), the function is
disabled.
The following values are usual:
Mobile wireless networks: 10
Wireless or satellite transmission: 0 .. 1
Call parameters
Dialing command
Dialing command for the local modem
Possible values:
D (AT command)
DP (AT command, pulse dialing)
DT (AT command, tone dialing)
When possible use the dialing command "D".
Dialing prefix
Access number (outside line) for a private branch exchange (typical entry 0 or 9) or for an
alternative telephone provider.
Permitted range: Max. 12 digits
With direct connection to the dial-up network and without an alternative telephone
provider, this parameter can remain empty.
Own phone number
Entry of your own telephone number for the network node including the area code.
Permitted values:
Digits 0 ... 9
Plus character (+) as placeholder for the trunk prefix (usually 00 or 09) before the
international area code
Example: +1230123456789

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens TIM 1531 IRC and is the answer not in the manual?

Siemens TIM 1531 IRC Specifications

General IconGeneral
BrandSiemens
ModelTIM 1531 IRC
CategoryController
LanguageEnglish

Related product manuals