Code
Fault
Description
Possible Cause
Solution
Open phase for output
Check the motor and output wiring for loose connections
77
Speed deviation
Acceleration time is too
short
Extend the acceleration time
Overloaded
Reduce the load
Current limit is too low
Increase the limit value in the allowable range
78
(In
accelerated run
ning)
Bus over-voltag
e protection
Abnormal input
power voltage
Check the input power
The motor is quick restarted
again in high-speed rotation
Stop and restart the motor
(In decelerated
running) bus
over-voltage
protection
Excessive load inertia
Use appropriate braking components
Deceleration time is too
short
Extend the deceleration time
The braking resistor has an
extremely large value or is
disconnected
Connect the appropriate braking resistor
(In constant
speed operation
) bus
over-voltage
protection
Exceptional input power
Check the input power
Excessive load inertia
Use appropriate braking components
The braking resistor has an
extremely large value or is
disconnected
Connect the appropriate braking resistor
79
Bus under
voltage
Supply voltage falls
below the
minimum operating voltage
Check the input power
Instantaneous power failure
Check the input power. When the input voltage is
normal, restart after reset
Significant changes in input
power voltage
The power wiring terminal is
loose
Check the input wiring
Abnormal internal switching
power
Ask professional technical personnel for Ispection
Large starting
current load in the
same power system
Changes the power system to meet the specifications
80
Open phase for
output
Abnormal, or ignored
connection or disconnection
in converter output side
connection
Follow the rules and check the converter output side
connections, eliminate missing and disconnection
Output terminal is loose
Electrical power is too
small, 1 / 20 or less of the
maximum applicable
motor capacity in
the converter
Adjust converter capacity or motor capacity
Unbalanced
output three-phase
Check whether the motor wiring is intact