Index Name R/W Description
13
DisCra
*
Flag analog chronology:
can be associated to any analog chronology
configuration to inhibit recording. When at value ‘1’, inhibits
recording in Database.
14
DisSam
-
(Not used)
15
DisAla
-
Flag sending alarm:
can be associated to any Alarm condition. When
at value ‘1’, inhibits the sending of alarm.
16
DaySav
-
Time:
1 = summer time (the ASPE ZoneBias = + 3600 seconds).
0 = wintertime.
17
PrgEnb
*
Program Enable:
when reset to ‘0’, allows stopping the execution of
BASIC/Ladder program. It can be useful to execute the program
manually (see next).
18
PrgOnc
1
Program Once:
when set to ‘1’, executes the cycle of BASIC/Ladder
program once. Useful for debugging the program.
TB
OX
MS resets the variable automatically.
19
TcpIpLog
*
TCP Logging:
Setting this register activates the Debugging of TCP/IP
connection. Very useful to trace problems when sending e-mail or
FTP. (see chapter 11.5)
When this option has been activated, the information is available
from TWinSoft main menu: ‘Communication’ ‘Download’
‘TCP/IP debugging’.
20
ALAovf
*
Alarm Overflow:
overflow in the stack of alarms. The size of the
stack of alarms can be adjusted from the ‘Advanced’ properties of
the RTU
21
ComErr
0
Communication error:
general communication error flag. It means
that one of the communication port (of the CPU or of a
communication card) used as ‘Master’ has encounter a
communication error. (SET)
22
SmtpEr
0
Smtp Error:
an error occurred while sending an e-mail. (SET)
23
FtpErr
0
Ftp Error:
an error occurred while sending files. (SET)
24
NTPErr
0
NTP Error:
an error occurred while setting time of TB
OX
MS. (SET)
25
GpsVF
-
GPS:
GPS validity. GPS returns a valid signal.
Validity of the signal. When changes to one, it indicates the GPS
receives sufficient signals to calculate its position (from minimum 3
satellites).
When changing from 0 to 1, the time of TB
OX
MS is set to the time
of GPS, with correction in regards to GMT according to the location
of TBox.
If you want to update the time manually, you reset the variable
26
GPRSErr
0
GPRS Error:
an error occurred during GPRS connection. TB
OX
MS
does not succeed to connect (not supported yet) (SET)
27
ModemLog
*
ModemLog:
authorizes the modem connection to be logged into
chronology. The communication port is declared in the ASV.24
[PortIdLog].
The ASV.25 [EventLog] must be tagged also.
The information is available in from the communication Download
TraceLog (not supported yet)
28
SystemEr
0
SystemErr:
the RTU detected an error during starting. Typically a
problem with a card (not supported yet) (SET)