12.3. Analog Alarm Condition
Tagname: The Tag selected to generate the alarm.
Type: Maximum or Minimum.
The threshold for which the alarm will be started. If the value of the analog Tag
passes under (minimum) or over (maximum) this threshold, the alarm is
started. If an alarm must be generated for both a maximum and a minimum
threshold, 2 conditions must be declared with the same Tag.
Value: The threshold value, depending on the format defined when creating the Tag
(see chapter 10.
The Tags
).
Hysteresis: The amount that the level must fall or rise below or above the Max. or Min.
value before an alarm can be re-started
Recipient: Select a Recipient or a group of recipients. The ‘person’ you wish to contact
in case of alarm (see ‘Recipients’ below).
In case you select a ‘group of Recipients’, TB
OX
MS calls the first one in the
group. In case the alarm cannot be acknowledged after the number of tries,
TB
OX
MS automatically calls the next Recipient in the group.
It is the equivalence to ‘Chain’ with previous generation of RTU, the