Version: 1.06 88
Handling: The handling option allows blocking each alarm condition, manually or
automatically.
Enabled:
alarm condition always active.
Disabled:
alarm condition always de-activated.
PowerF:
alarm condition disabled when there is a main power failure.
DisAla:
alarm condition de-activated when the system variable ‘DisAla’ is at 1.
Severity: Each alarm can be assigned a level of severity: Low, Normal or High. When
several alarms are still present in the queue and then not processed yet,
TB
OX
MS generates the calls according to the highest severity.
End of Alarm: When the alarm condition is finished, an alarm is automatically sent to the
same recipient with the same message.
Example:
for a ‘positive edge’ alarm, it is when the Tag returns to ‘0’.
It is also useful when the alarm condition is active when TB
OX
MS starts up.
When ‘end of alarm’ is checked, an alarm is automatically generated when the
alarm condition disappears (see illustration chapter 12.7:
Alarms table
)
Call all Recipients: In case you select a group of Recipients, TB
OX
MS executes a
link between recipients: it calls all Recipients one after each
other.