Section 5 – SR-2 Diagnostics
63 ENGINE STOPPED
Page 1 of 2
Alarm Type
Log, Prevent or Shutdown Alarm
Associated Alarm
Codes
Alarm Code 84 Restart Null
How Alarm is Set
1. The unit was running, and still should be, but has stopped.
2. Unit not running is determined based on multiple factors, and can be caused by an intermittent condition.
3. Three attempts will be made to allow continued operation at temporarily reduced performance. If at the
end of the three attempts full performance is not possible, the alarm is set as a Shutdown alarm.
If continuous restarts are enabled, a Shutdown alarm is not set after 3 attempts.
If restarts are disabled, the alarm will be set as a Shutdown alarm on the first occurrence.
4. If Alarm Code 17 Engine Failed to Crank, or Alarm code 20 Engine Failed to Start alarm occurs after Alarm
Code 63 is cleared, the Alarm Code 17 or Alarm Code 20 will be set as a Shutdown alarm.
How Alarm is Cleared
This alarm is cleared manually or automatically.
Programmable Features
Unit can be programmed for continuous restarts.
Considerations
Becomes a log alarm if unit is switched to electric mode.
5-58
02 February 2005