Section 5 – SR-2 Diagnostics
63 ENGINE STOPPED
Page 2 of 2
Diagnostic Procedure
1. Perform a Pretrip Test to determine cause for shutdown.
2. Check the fuel level.
3. Check the fuel pump for proper operation.
4. Check the air cleaner and intake hose for obstructions.
5. Check the unit fuses.
6. Check the RPM sensor for proper operation.
7. Check Run Relay and fuel solenoid components and circuits.
8. Check for low battery voltage.
9. Be sure all ground connections on the master ground plate are secure.
10. Check for a seized compressor or engine.
11. If a Model 50 electric standby unit, check for a failed clutch or seized electric motor.
64 PRETRIP REMINDER
Page 1 of 1
Alarm Type
Log Alarm
Associated Alarm
Codes
How Alarm is Set
A programmable hour meter was set as a Pretrip Reminder, and the hourmeter time has expired.
How Alarm is Cleared
Alarm self-clears when a Pretrip Test is completed successfully.
Programmable Features
This feature must be programmed. See Section 3 Hourmeters for details.
Diagnostic Procedure
1. Perform a Pretrip Test to confirm unit operation.
2. Reset the Pretrip Reminder hourmeter after successful test completion.
5-59
02 February 2005

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thermo King SR-2 SmartReefer2 and is the answer not in the manual?

Thermo King SR-2 SmartReefer2 Specifications

General IconGeneral
BrandThermo King
ModelSR-2 SmartReefer2
CategoryControl Systems
LanguageEnglish

Related product manuals