Section 3 – SR-2 Software Description
Unit Configuration Setup Menu
The Unit Setup Menu is used to specify the actual
unit configuration. These features are set at the
factory as required for each unit. The factory
settings shown below are for a replacement
microprocessor.
Alarm Code 111 Unit Not Configured Correctly
If the microprocessor detects a mismatch between
unit connections and configuration selections, Alarm
Code 111 Unit Not Configured Correctly will be set.
Engine Type Is
Micro Rev
All
HMI Rev
All
Choices
Factory Set
Yanmar 2.1
Exceptions
Description This feature allows the engine type
to be selected. Currently only Yanmar 2.1 is
available.
Compressor Type Is
Micro Rev
All
HMI Rev
All
Choices
Recip or Screw
Factory Set
Reciprocating
Exceptions
Description This feature allows the compressor
type to be selected. The screw option is for a future
implementation and should not be selected.
ETV Configured
Micro Rev
All
HMI Rev
All
Choices
YES or NO
Factory Set
YES
Exceptions
Description This feature allows the unit to be
configured with an Electronic Throttling Valve (ETV).
Units with ETV valve should be set YES. All other
units should be set NO.
Electric Standby Equipped?
Micro Rev
All
HMI Rev
All
Choices
YES or NO
Factory Set
To match unit as built
Exceptions
Description This feature specifies if the unit is
equipped with optional electric standby. If the unit is
equipped with electric standby, this feature should
be set Yes. If the unit is not equipped with electric
standby, this feature should be set No.
Electric Motor Type Is
Micro Rev
All
HMI Rev
All
Choices
2 Pole or 4 Pole
Factory Set
4 Pole
Exceptions The 2 pole is a future option and
should not be selected
Description Current units with electric standby
should be set for a 4-pole motor.
Diesel to Electric Auto Switch Enabled?
Micro Rev
All
HMI Rev
All
Choices
YES or NO
Factory Set
NO
Exceptions
Description This feature allows the Auto Switch
from Diesel to Electric to be enabled or disabled. If
this feature is set YES, the unit will switch
automatically to electric mode when standby power
is connected. If the feature is set NO, the operator
must physically switch the unit to electric mode.
3-44
31 January 2005