Section 3 – SR-2 Software Description
Continuous Door Open Forces
Micro Rev
All
HMI Rev
All
Choices
Off or Log Only
Factory Set
Log Only
Exceptions
Description If the optional door switch is
installed this feature allows the Door Open action for
the selected range to be set. If this feature is set
OFF the unit will shut the unit down and log the door
opening 4 seconds after the door is opened. If the
unit is in defrost when the door is opened the defrost
cycle will be completed before the unit shuts down.
If this feature is set LOG ONLY the door opening will
be logged after 4 seconds but the unit will continue
to run.
Door openings are logged in both the CargoWatch
and ServiceWatch data loggers. The door switch
must be open or closed for 4 seconds before the
event is logged to prevent false readings.
Door Open Timeout
Micro Rev
All
HMI Rev
All
Choices
Off, 1 hour to 4 hours in 10-minute
increments
Factory Set
Off
Exceptions Only appears if Continuous Door
Open Forces (above) = Off.
Description This feature allows the unit to restart
if the door open time exceeds the set limit.
Door Open Timeout for the selected range can be
set to Off or for a time limit from 1 to 4 hours, in 10-
minute increments. If set Off the unit will remain off
until the door is closed. If a time period is selected
the unit will restart and run 4 seconds after the time
period elapses. The unit will continue to run even if
the door is still open.