Section 5 – SR-2 Diagnostics
108 DOOR OPEN TIMEOUT
Page 1 of 1
Alarm Type
Check Alarm
Associated Alarm
Codes
How Alarm is Set
If a door switch installed, the unit is programmed to shut off on door opening, and restart if a maximum door open
time is programmed and time has expired.
How Alarm is Cleared
This alarm is cleared manually.
Considerations
If the unit is programmed to force the unit to null when the door switch is open, the unit will not re-enter null until
after the door switch is closed and then re-opened.
Diagnostic Procedure
Check the operation of the door switches.
111 UNIT NOT CONFIGURED CORRECTLY
Page 1 of 1
Alarm Type
Log or Check Alarm (Pretrip Test Only)
Associated Alarm
Codes
Alarm Code 74 Controller Reset to Defaults
Alarm Code 92 Sensor Grades Not Set
How Alarm is Set
Alarm is set during a Pretrip Test if a mismatch exists between the unit hardware configuration and the unit
hardware, as detected by the microprocessor.
How Alarm is Cleared
This alarm is cleared manually.
Diagnostic Procedure
1. Verify actual unit configuration.
2. Set the unit configuration using the Unit Configuration sub-menu of the Programming Menu, as shown in
Service Procedure A04A.