E6582062
6-21 6. [Advanced] How to use parameters
3
4
6
9
<F229: AI5 point 1 frequency>
<F230: AI5 point 2 input value>
<F231: AI5 point 2 frequency>
<F810: Communication frequency point select>
<F811: Communication point 1 input value>
<F812: Communication point 1 frequency>
<F813: Communication point 2 input value>
<F814: Communication point 2 frequency>
Function
These parameters set the output frequencies for the frequency commands of the analog signals.
You can use the following terminals. The terminals [AI4] and [AI5] are optional.
Voltage input (0 to 10 V) : terminals [RR], [RX], [AI4], and [AI5]
Voltage input (-10 to +10 V) : terminals [RX], [AI4], and [AI5]
Curret input (4 to 20 mA) : terminals [II], [AI4], and [AI5]
Parameter setting
Title Parameter name Adjustment range Unit Default setting
F107 Terminal RX input
voltage select
0: 0 to +10 V
1: -10 to +10 V
-0
F108 Terminal RR input select 1: Voltage input (0-10 V)
2: -
3: -
4: PTC input
5: PT100 (2-wire) input
6: -
7: PT1000 (2-wire) input
8: -
9: KTY84 input
-1
F148 Terminal AI4 input select 1: Voltage input (0-10 V)
2: Voltage input (-10 to +10 V)
3: Current input (0-20 mA)
4: PTC input
5: PT100 (2-wire) input
6: PT100 (3-wire) input
7: PT1000 (2-wire) input
8: PT1000 (3-wire) input
9: KTY84 input
-1
F149 Terminal AI5 input select 1
F201 RR point 1 input value 0-100 % 0
F202 RR point 1 frequency 0.0-590.0 Hz 0.0
F203 RR point 2 input value 0-100 % 100
F204 RR point 2 frequency 0.0-590.0 Hz
50.0/60.0
*1
F205 RR point 1 rate 0-250 % 0
F206 RR point 2 rate 0-250 % 100
F209 Analog input filter 1: Disabled
2-1000 ms
1