E6582062
6-25 6. [Advanced] How to use parameters
3
4
6
9
The allowance is zero setting on default setting.
Parameter setting
Adjustment method
For the frequency commands to be input to the analog terminals and the output frequency
characteristics, refer to the following figure.
Analog input terminal bias adjustment (<F470>, <F472>, <F474>, <F476>, and <F478>)
To avoid the influence of noise, there is a tolerance for the minimum input amount so that the
inverter starts output after some voltage/current is applied to the analog input terminal by default
setting.
To decrease this tolerance value, increase the bias value for a corresponding terminal.
However, if the set value is too large, frequency may be output even when the frequency command
is set to 0 (zero).
Analog input terminal gain adjustment (<F471>, <F473>, <F475>, <F477>, and <F479>)
The set maximum frequency is output before voltage/current reach the maximum value to avoid
trouble such as voltage drop by default setting.
Title Parameter name Adjustment range Unit Default setting
F470 RR input bias 0-255 - 128
F471 RR input gain 0-255 - 128
F472 RX input bias 0-255 - 128
F473 RX input gain 0-255 - 128
F474 II input bias 0-255 - 128
F475 II input gain 0-255 - 128
F476 AI4 input bias 0-255 - 128
F477 AI4 input gain 0-255 - 128
F478 AI5 input bias 0-255 - 128
F479 AI5 input gain 0-255 - 128
0%
0V
4mA
100%
10Vdc
20mAdc
Output frequency (Hz)
Default setting
Point 2 frequency
Large
Large
Small
Small
Frequency command signal
0
<F471>
<F473>
<F475>
<F470>
<F472>
<F474>

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m