EasyManua.ls Logo

Toshiba TOSVERT VF-AS3 - Page 329

Toshiba TOSVERT VF-AS3
622 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6582062
6-87 6. [Advanced] How to use parameters
3
4
6
9
Increasing this value will increase the exciting current.
Keep in mind that setting a value too high will cause hunting in the motor.
<F417: Motor rated speed>
This parameter sets the motor rated speed.
Check the motor name plate or test report while setting.
6) Motor parameter setting method (Advanced)
How to adjust the moment of inertia of the load
<F459: Load inertia ratio>
This parameter adjusts the excess response speed.
Increasing this value will reduce the overshoot at the acceleration/deceleration completion
point.
Default setting values are set so that the moment of inertia of the load (including the motor
shaft) value is set to be appropriate at 100% of the motor shaft. If the moment of inertia of the
load is not 100%, set a value appropriate for the actual inertia of the load.
<F460: Speed control response 1>
<F461: Speed control stabilization coefficient 1>
<F462: Speed reference filter coefficient 1>
<F463: Speed control response 2>
<F464: Speed control stabilization coefficient 2>
<F465: Speed reference filter coefficient 2>
<F466: Speed control response switching frequency>
This parameter adjusts the excess response speed.
Increasing this value will reduce the overshoot at the acceleration/deceleration completion
point. Set a value appropriate for the actual inertia of the load.
For details, refer to "Current and Speed Control Gain Adjustment Method" manual (E6582136).
If the torque needs to be increased in low speed range (10Hz or less as a guide)
Perform the basic settings for the motor parameters. Then, if the torque needs to be
increased even further, increase <F413: Exciting current coefficient> to a maximum of 130%.
<F413> is a parameter that increases the magnetic flux of the motor at low speeds, so
specifying a higher value for <F413> increases the no-load current. If the no-load current
exceeds the rated current, do not adjust this parameter.
If the motor stalls when operated at frequencies over the base frequency
Adjust <F414: Stall prevention coefficient>.
If a heavy load is applied momentarily (transiently), the motor may stall before the load
current reaches the stall prevention level (<F601>, etc.). In such a case, a motor stall may be
avoided by reducing the value of <F414> gradually.
Memo
To use vector control, the motor capacity must be the same as the inverter rated capacity, or
you can use a general purpose squirrel-cage motor with capacity no less than one rank below.
Note that the minimum applicable motor capacity is 0.1 kW.

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Related product manuals