E6582062
6. [Advanced] How to use parameters 6-144
4
4
6
9
6. 30. 17 Setting parts replacement alarm by the ambient
temperature
<F634: Annual average ambient temperature>
Function
Based on the inverter ON time (cumulative power ON time), motor run time (cumulative run time),
cooling fan run time (cumulative cooling fan run time), output current , and <F634: Annual average
ambient temperature>, the time of replacement of the cooling fan, power circuit capacitor, and
capacitor mounted on a printed circuit board is calculated. When the time of replacement
approaches, the alarm can be output on the monitor display and output terminal.
Parameter setting
Selecting a setting value
Set the annual average temperature around the inverter. (This is not the annual highest
temperature.)
Signal output of parts replacement alarm
Assign the parts replacement alarm to the unused output terminal. For details, refer to [7. 2. 2].
"128: Parts replacement alarm"
"160: Cooling fan replacement alarm"
Monitor display of parts replacement alarm
Parts replacement alarm information (refer to [8. 1. 1]) can be checked in the [Monitor mode].
Title Parameter name Adjustment range Default setting
F634 Annual average ambient
temperature
1: -15 to +10°C
2: +11 to +20°C
3: +21 to +30°C
4: +31 to +40°C
5: +41 to +50°C
6: +51 to +60°C
3
Important
Set <F634: Annual average ambient temperature> when installing the inverter. After the
installation, this setting should not be changed. Otherwise, calculation of parts replacement
alarm may have an error.
0.0HzSTOP
14:03
F634 : Ambient temperature
3: +21to+30
4. +31to+40
5. +41to+50
6. +51to+60
1. -15to+10