E6582062
6-173 6. [Advanced] How to use parameters
3
4
6
9
6. 34. 8 Clearing run command
<F719: Run command clear select>
Function
This parameter is used to select whether the run command is retained or cleared when the following
events occur during panel run or RS485 communication run.
Coast stop with standby function (ST) is off (OFF display)
Coast stop with coast command function (FRR) is on (OFF display)
Power circuit undervoltage (MOFF) alarm
Parameter setting
Difference between the settings
Title Parameter name Adjustment range Default setting
F719 Run command clear
select
0: Clear at coast stop. Retain when MOFF
occurs and CMOd is changed.
1: Retain run command.
2: Clear at coast stop and at MOFF. Retain
when CMOd is changed.
3: Clear at coast stop, at MOFF and when
CMOd is changed.
2
<F719> setting value Coast stop
When power circuit
undervoltage (MOFF)
alarm occurred
When <CMOd> is
changed
0 Run command clear Retain run command
1 Retain run command
2 Run command clear Retain run command
3 Run command clear
Important
If "PrA" alarm occurs when STO activated, run command is cleared regardless of the <F719>
setting.
0: Clr at coast stop
1: Retain run command
0.0HzSTOP
14:14
F719 : Run command clear select
2: Clr at coast stop & MOFF
3: Clr at coast stop, MOFF & Cmod

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals