E6582062
2-9 2. Installation and wiring
2
3
9
10
When more than one inverter are installed in one cabinet
When two or more inverters are installed in one cabinet, pay attention to the followings.
Ensure a space of at least 20 cm or more on the top and bottom of the inverters.
(Note: Depending on the inverter type.)
Install an air deflecting plate so that the heat rising up from the inverter on the bottom does not
affect the inverter on the top.
Inverters may be installed side by side with each other with no space left between them.
When installing inverters side by side, remove the top cover of the inverter. For how to remove,
refer to [2. 2].
When using the inverter in locations with temperatures above 50°C, use the inverter with the oper-
ation panel removed and the output current reduced.
Inverter
Inverter
Air
deflecting
plate
Ventilation fan

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m