E6582062
7-3 7. Operating using external signals
3
4
7
9
RES F113 Terminal RES function 1
0 - 203
*1
8
F153 Terminal RES function 2 0
F157 Terminal RES function 3 0
S1 F114 Terminal S1 function 1
0 - 203
*1
10
F154 Terminal S1 function 2 0
F158 Terminal S1 function 3 0
S2 F115 Terminal S2 function 0 - 203 12
S3 F116 Terminal S3 function 0 - 203 14
S4 F117
Terminal S4 function
*2
0 - 203 16
F146 Terminal S4 input select 0: Digital input
1: Pulse train input
2: PG input
0
S5 F118
Terminal S5 function
*3
0 - 203 118
F147 Terminal S5 input select 0: Digital input
1: Pulse train input
2: PG input
0
DI11 F119
Terminal DI11 function
*4
0 - 203 0
DI12 F120
Terminal DI12 function
*4
0 - 203 0
DI13 F121
Terminal DI13 function
*4
0 - 203 0
DI14 F122
Terminal DI14 function
*4
0 - 203 0
DI15 F123
Terminal DI15 function
*4
0 - 203 0
DI16 F124
Terminal DI16 function
*4
0 - 203 0
F F140 Terminal F response time 1 - 1000 (ms)
1
*5
R F141 Terminal R response time 1 - 1000 (ms)
1
*5
RES F142 Terminal RES response time 1 - 1000 (ms)
1
*5
S1 F143 Terminal S1 response time 1 - 1000 (ms)
1
*5
S2 - S5 F144 Terminal S2-S5 response time 1 - 1000 (ms)
1
*5
DI11-DI16 F145
Terminal DI11-DI16 response time
*4
1 - 1000 (ms)
1
*5
*1 If a variety of functions are assigned to a terminal, the assigned functions will be simultaneously enabled.
*2 When you use the terminal [S4] as digital input, set <F146: Terminal S4 input select> = "0: Digital input".
*3 When you use the terminal [S5] as digital input, set <F147: Terminal S5 input select> = "0: Digital input".
*4 Indicated optional terminals on IO extension 1 (ETB013Z), refer to E6582128.
*5 If stable operation cannot be achieved because of noise of the frequency setting circuit, etc., increase the values for <F140: Terminal F
response time> to <F145: Terminal DI11-DI16 response time>.
Terminal
symbol
Title Parameter name Adjustment range
Default
setting