E6582062
11-15 11. Table of parameters
1
3
9
10
11
F307 0307
Supply voltage
compensation,
Output voltage
limitation
0: Without supply
voltage
compensation,
Limited output voltage
1: With supply voltage
compensation,
Limited output voltage
2: Without supply
voltage
compensation,
Unlimited output
voltage
3: With supply voltage
compensation,
Unlimited output
voltage
--
*2
N [6. 15. 6]
F308 0308 Braking resistance 0.5 - 1000 Ω
*1
N
[6. 15. 4]
F309 0309
Braking resistor
capacity
0.01 - 600.0 kW
*1
N
F310 0310
Dec time at power
failure
0.0 - 320.0 s 2.0 N [6. 15. 2]
F311 0311 Reverse inhibited
0: Allowed
1: Rev inhibited
2: Fwd inhibited
3: -
4: -
- - 0 N [6. 15. 7]
F312 0312 Random switching
0: Disabled
1: Random switching 1
2: Random switching 2
3: Random switching 3
- - 0 N [6. 14]
F313 0313 Ridethrough time
0.0: Continuous
0.1 - 320.0
s 2.0 N [6. 15. 2]
F314 0314
Parameter for
manufacturer
------
F315 0315
Parameter for
manufacturer
------
F316 0316
Carrier frequency
control
0: No decrease
1: Valid decrease
2: No decrease, 480V
class
3: Valid decrease, 480V
class
4: No decrease with
sinusoidal filter
5: Valid decrease with
sinusoidal filter
--
*1
N
[2. 4. 1]
[6. 14]
F317 0317
Synchronized stop
time
0.0 - 6000 s 2.0 Y
[6. 15. 2]
F318 0318
Synchronized reach
time
0.0 - 6000 s 2.0 Y
F319 0319
Regenerative over-
flux upper limit
100 - 160 %
*2
N [6. 15. 5]
Title
Communication
No.
Parameter name Adjustment range Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference