EasyManuals Logo
Home>Toshiba>Inverter>TOSVERT VF-AS3

Toshiba TOSVERT VF-AS3 User Manual

Toshiba TOSVERT VF-AS3
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #303 background imageLoading...
Page #303 background image
E6582062ï‚‚
6-61 6. [Advanced] How to use parameters
3
4
6
9
6. 15. 4 Dynamic braking - Abrupt motor stop
<F304: Dynamic braking, OLr trip>
<F308: Braking resistance>
<F309: Braking resistor capacity>
<F626: Overvoltage limit operation level>
<F639: Braking resistor overload time>
â–  Function
The dynamic braking function can be enabled by connecting an external braking resistor.
• When an abrupt deceleration is necessary
• When an overvoltage "OP" trip occurs at a deceleration stop
• When the continuous regenerative state, such as moving down of a lifting gear and winding-out
operation for tension control, is entered
• When the regenerative state is entered by load fluctuation during constant speed run of a press
machine, etc.
â–  Parameter setting
â–  How to use
To use dynamic braking, set <F304: Dynamic braking, OLr trip> to "1" - "8" (dynamic braking
enabled). At this time, the overvoltage limit operation is automatically disabled as in the case of
<F305: Overvoltage limit operation> ="1: Disabled", and the regenerative energy of the motor is
consumed by a braking resistor. (Refer to [6. 15. 5].)
Title Parameter name Adjustment range Unit Default setting
F304 Dynamic braking, OLr trip 0: Disabled
1: Enabled, OLr trip
2: Enabled, No OLr trip
3: Enabled (except during ST OFF), OLr trip
4: Enabled (except during ST OFF), No OLr
trip
5: Enabled (except during trip), OLr trip
6: Enabled (except during trip) ,No OLr trip
7: Enabled (except during trip & ST OFF),
OLr trip
8: Enabled (except during trip & ST OFF), No
OLr trip
0
F308 Braking resistance 0.5 - 1000 Ω
*1
*1 Depending on capacity, refer to [11. 6].
F309 Braking resistor capacity 0.01 - 600.0 kW
*1
F626 Overvoltage limit
operation level
100 - 150 % 134
F639 Braking resistor overload
time
0.1 - 600.0 s 5.0
0: Disabled
1: Enabled,OLr trip
2: Enabled,No OLr trip
3: Enabled (exc ST off) ,OLr
4: Enabled (exc ST off) ,No OLr
0.0HzSTOP
13:17
F304 : Dynamic braking,OLr trip

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS3
CategoryInverter
LanguageEnglish

Related product manuals