E6582062ï‚‚
6. [Advanced] How to use parameters 6-60
4
4
6
9
During retry, "rtry" is displayed on LCD screen.
The retry count is cleared (number of retry: 0) after a specified time without occurrence of trips from
a retry success.
A retry success means that the output frequency reaches the frequency command value without
tripping.
Important
• A failure signal is not output during retry.
A "10: Failure signal 1" is allocated to the [FLA]-[FLB]-[FLC] terminals in the default setting.
• To output a failure signal during retry, allocate the function "116: Failure signal 4" or "117" to the
output terminal.
• The virtual cooling time is provided for the overload trips "OL1", "OL2", and "OLr".
A retry is performed after the virtual cooling time and retry time elapse.
• For the overvoltage trips "OP1", "OP2" and "OP3", a retry is performed after the voltage in the
DC section decreases.
• For the overheat trip "OH", a retry is performed after the inverter internal temperature
decreases to the operable level.
Reference
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
• Details on operation by external signals -> Refer to [Chapter 7].

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS3
CategoryInverter
LanguageEnglish

Related product manuals