E6582062
11-39 11. Table of parameters
1
3
9
10
11
F730 0730
Panel frequency
setting lockout
0: Unlocked without
press OK
1: Locked
2: Unlocked after press
OK
--2Y
[6. 34. 1]
F731 0731
Operation after
disconnection
detection during
panel run
1: Continue running
2 - 3: -
4: Trip
--4Y
F732 0732
Panel Hand/Auto
function lockout
0: Unlocked
1: Locked
--1Y
F733 0733 Panel Run lockout
0: Unlocked
1: Locked
--0Y
F734 0734
Panel emergency
off lockout
0: Unlocked
1: Locked
--0Y
F735 0735 Panel reset lockout
0: Unlocked
1: Locked
--0Y
F736 0736
CMOd/FMOd
change lockout
during run
0: Unlocked
1: Locked
--1Y
F737 0737 Panel keys lockout
0: Unlocked
1: Locked
2: Locked only
extension panel
3: Locked only operation
panel
--0Y
F738 0738 Password setting
0: Disabled
1 - 9998
9999: Password was set
--0Y
F739 0739
Password
verification
0: non-setting
1 - 9998
9999: Password was set
--0Y
F740 0740 Trace
0: Disabled
1: At trip
2: At trigger input
3: At trip & at trigger
input
--1Y
[6. 35]
F741 0741 Trace cycle
0: 4ms
1: 20ms
2: 100ms
3: 1s
4: 10s
--2Y
F742 0742 Trace data 1
0 - 162
*3
--0Y
F743 0743 Trace data 2 - - 1 Y
F744 0744 Trace data 3 - - 2 Y
F745 0745 Trace data 4 - - 3 Y
F748 0748
Cumulative power
save
0: Disabled
1: Enabled
--0Y
[6. 36]
F749 0749
Cumulative power
unit
0: 1.0=1 kWh
1: 1.0=10 kWh
2: 1.0=100 kWh
3: 1.0=1000 kWh
4: 1.0=10000 kWh
5: 1.0=100000 kWh
--*1Y
Title
Communication
No.
Parameter name Adjustment range Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m