E6582062
11. Table of parameters 11-42
1
9
11
F800 0800
RS485 (1) baud
rate
0: 9600 bps
1: 19200 bps
2: 38400 bps
3: -
--1Y
[6. 38. 1]
F801 0801 RS485 (1) parity
0: Disabled
1: Even parity
2: Odd parity
--1Y
F802 0802
Inverter number
(RS485 common)
0 - 247 - - 0 Y
F803 0803
RS485 (1) time-out
time
0.0: Disabled
0.1 - 100.0
s0.0Y
F804 0804
RS485 (1) time-out
operation
1: Continue running
2, 3: -
4: Trip
5: -
6: Trip after deceleration
stop
--1Y
F805 0805
RS485 (1)
transmission wait
time
0.00 - 2.00 s 0.00 Y
F806 0806
RS485 (1) inverter
to inverter
communication
0: Follower (0Hz
command when
Leader fails)
1: Follower (continue
running when Leader
fails)
2: Follower (emergency
off when Leader fails)
3: Leader (transmit
frequency command)
4: Leader (transmit
output frequency
signal)
5: Leader (transmit
torque command)
6: Leader (transmit
output torque)
--0Y
F807 0807 RS485 (1) protocol
0: TOSHIBA
1: MODBUS
--0Y
F808 0808
RS485 (1) time-out
detection
0: Always
1: Run command and
frequency command
by communication are
enabled.
2: During run by
communication
--1Y
F809 0809
Operation panel
connection priority
0: By the parameter
setting
1: Connect to conector 1
2: Connect to conector 2
--1Y -
Title
Communication
No.
Parameter name Adjustment range Unit
Minimum
setting unit
(Panel/
Communication)
Default
setting
Write
during
running
*6
User
setting
Reference

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m