E6581158
H-7
8
(Continued)
Error code
Failure
code
Description
QER
0025 Overcurrent flowing in element during acceleration
QER 0026 Overcurrent flowing in element during deceleration
QER
0027 Overcurrent flowing in element during constant-speed operation
GVP 0054 Auto-tuning error
GV[R
0029 Inverter type error
QJ 002E External thermal input
G
0032 VIA cable break
G 0033 Communication error between CPUs
G
0034 V/F control error
G 0035 CPU fault 2
UQWV
002F Step-out (for PM motors only)
(Note) Past trip records (trip records retained or trips that occurred in the past) can be called up.
(Refer to 8.1 "Status monitor mode" for the call-up procedure.)
(*) Strictly speaking, this code is not an error code; this code is displayed to show the absence of error
when the past trip monitor mode is selected.
8.2.2 Display of trip information at the occurrence of a trip
At the occurrence of a trip, the same information as that displayed in the mode described in 8.1.1, "Status monitor
under normal conditions," can be displayed, as shown in the table below, if the inverter is not turned off or reset.
To display trip information after turning off or resetting the inverter, follow the steps described in 8.1.2, "Display of
detailed information on a past trip."
Q Example of call-up of trip information
Item displayed
Key
operated
LED
display
Communi-
cation No.
Description
Cause of trip
QR
Status monitor mode (The code blinks if a trip oc-
curs.)
The motor coasts and comes to a stop (coast stop).
Parameter setting
mode
CWJ
The first basic parameter “CWJ” (history function)
is displayed.
Direction of
rotation
HT-H FE01
The direction of rotation at the occurence of a trip
is displayed. (HTH: forward run, HTT:
reverser run).
Operation fre-
quency command
H
FE02
The operation frequency command value (Hz/free
unit) at the occurrence of a trip is displayed.
Load current E FE03
The output power of the inverter at the occurrence
of a trip (%/A) is displayed.
Input voltage [ FE04
The inverter input (DC) voltage (%/V) at the
occurrence of a trip is displayed.
Output voltage R FE05
The output voltage of the inverter at the
occurrence of a trip (%/V) is displayed.
(Continued overleaf)
MO
MOMO
MODE
DEDE
DE
MO
MOMO
MODE
DEDE
DE
Note 3
Note 2
Note 1

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)

Related product manuals