9
Table 2 Combinations of inverter and EMI filter
Three-phase 200V class
Combination of inverter and filter
Inverter Transmission noise
CISPR/B/276/DC Class A Group 1
Applicable filters
(Length of motor connecting cable:
Max. 5 m)
Transmission noise
EN55011 Class B Group 1
Applicable filters
(Length of motor connecting cable:
Max. 1 m)
VFS11-2002PM EMFS11-2007AZ
VFS11-2004PM EMFS11-2007AZ
VFS11-2005PM EMFS11-2007AZ
VFS11-2007PM EMFS11-2007AZ
VFS11-2015PM EMFS11-4015BZ
VFS11-2022PM EMFS11-4015BZ
VFS11-2037PM EMFS11-4025CZ
VFS11-2055PM EMFS11-4047DZ
VFS11-2075PM EMFS11-4047DZ
VFS11-2110PM EMFS11-2083EZ
VFS11-2150PM EMFS11-2083EZ
Three-phase 400V class
Combination of inverter and filter
Inverter Transmission noise
CISPR/B/276/DC Class A Group 1
Applicable filters
(Length of motor connecting cable:
Max. 5 m)
Transmission noise
EN55011 Class B Group 1
Applicable filters
(Length of motor connecting cable:
Max. 20 m)
Transmission noise
EN55011 Class A Group 1
Applicable filters
(Length of motor connecting cable:
Max. 50 m)
VFS11-4004PL With a built-in filter EMFS11-4015BZ
VFS11-4007PL With a built-in filter EMFS11-4015BZ
VFS11-4015PL With a built-in filter EMFS11-4015BZ
VFS11-4022PL With a built-in filter EMFS11-4025CZ
VFS11-4037PL With a built-in filter EMFS11-4025CZ
VFS11-4055PL With a built-in filter EMFS11-4047DZ
VFS11-4075PL With a built-in filter EMFS11-4047DZ
VFS11-4110PL With a built-in filter EMFS11-4049EZ
VFS11-4150PL With a built-in filter EMFS11-4049EZ
Single-phase 200V class
Combination of inverter and filter
Inverter Transmission noise
CISPR/B/276/DC Class A Group 1
Applicable filters
(Length of motor connecting cable:
Max. 5 m)
Transmission noise
EN55011 Class B Group 1
Applicable filters
(Length of motor connecting cable:
Max. 20 m)
Transmission noise
EN55011 Class A Group 1
Applicable filters
(Length of motor connecting cable:
Max. 50 m)
VFS11S-2002PL With a built-in filter EMFS11S-2009AZ
VFS11S-2004PL With a built-in filter EMFS11S-2009AZ
VFS11S-2007PL With a built-in filter EMFS11S-2009AZ
VFS11S-2015PL With a built-in filter EMFS11S-2016BZ
VFS11S-2022PL With a built-in filter EMFS11S-2022CZ
(2) Use shielded power cables, such as inverter output cables, and shielded control cables. Route the cables
and wires so as to minimize their lengths. Keep a distance between the power cable and the control cable
and between the input and output wires of the power cable. Do not route them in parallel or bind them to-
gether, instead cross at right angle.