EasyManuals Logo

Toshiba TOSVERT VF-S11 User Manual

Toshiba TOSVERT VF-S11
269 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #254 background imageLoading...
Page #254 background image
E6581158
M-2
13
(Continued)
Error code Failure code Problem Possible causes Remedies
QR
000A Overvoltage during
acceleration
The imput voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyrister is connected
to the same power distribution line.
A restart signal is input to the rotating
motor after a momentary stop, etc.
Insert a suitable input reactor.
Use H (auto-restart) and H
(ride-through control).
QR
000B Overvoltage during
deceleration
The deceleration time FGE is too short.
(Regenerative energy is too large.)
H (dynamic braking resistor) is off.
H (overvoltage limit operation) is
off.
The input voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened and closed.
(3) A system using a thyrister is connected
to the same power distribution line.
Increase the deceleration time FGE.
Install a dynamic braking resistor.
Enable H (dynamic braking resis-
tor).
Enable H (overvoltage limit opera-
tion).
Insert a suitable input reactor.
QR
000C Overvoltage during
constant-speed op-
eration
The input voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyrister is connected
to the same power distribution line.
The motor is in a regenerative state be-
cause the load causes the motor to run at
a frequency higher than the inverter out-
put frequency.
Insert a suitable input reactor.
Install a dynamic braking resistor.
QN
000D Inverter overload
The acceleration time ACC is too short.
The DC braking amout is too large.
The V/F setting is improper.
A restart signal is input to the rotating
motor after a momentary stop, etc.
The load is too large.
Increase the acceleration time CEE.
Reduce the DC braking amount H
and the DC braking time H.
Check the V/F parameter setting.
Use H (auto-restart) and H
(ride-through control).
Use an inverter with a larger rating.
QN
000E Motor overload
The V/F setting is improper.
The motor is locked up.
Low-speed operation is performed con-
tinuously.
An excessive load is applied to the motor
during operation.
Check the V/F parameter setting.
Check the load (operated machine).
Adjust QNO to the overload that the
motor can withstand during operation in a
low speed range.
QNT
000F Dynamic braking re-
sistor
overload trip
The deceleration time is too short.
Dynamic braking is too large.
Increase the deceleration time FGE.
Increase the capacity of dynamic braking
resistor (wattage) and adjust PBR capac-
ity parameter H.
*
QV
0020 Over-torque trip
Over-torque reaches to a detection level
during operation.
Enable H (over-torque trip selec-
tion).
Check system error.
QJ
0010 Overheat
The cooling fan does not rotate.
The ambient temperature is too high.
The vent is blocked up.
A heat generating device is installed close
to the inverter.
The thermistor in the unit is broken.
Restart the operation by resetting the
inverter after it has cooled down enough.
The fan requires replacement if it does
not rotate during operation.
Secure sufficient space around the
inverter.
Do not place any heat generating device
near the inverter.
Make a service call.
* You can select a trip ON/OFF by parameters.
(Continued overleaf)

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)

Related product manuals